Structural Steel Design / Built-up Compression Members / Part 1 of 2

Lacing & Battening

Converted from handwritten notes — Steel Structure 4.pdf, pages 1–18

Doc No.SS-04-01
StatusDraft — Awaiting Review
Converted17-08-2026
Approved—

Lacing & Battening — Introduction

g s already decided

Two channel components spaced s apart, connected by lacing across the open faces — spacing s and back-to-back gauge g are treated as already decided (from the compression-member design) before lacing is designed.

c θ (40–70°) lacing flat

Single lacing (left) — bars crossing in a Z/N pattern, inclination θ between 40° and 70° to the column axis. Lacing flats without crossing joints (right) are better able to resist accidental failure.

double lacing

Double lacing — two interlocking sets of diagonal bars (front set black, rear set blue), used when single lacing cannot satisfy the local-buckling slenderness limit.

Design steps:

  1. Length → assumed from geometry.
  2. Force F — choose b, t (prove safety); satisfy for maximum λ.
  3. Connection — F/Rv = number of rivets.

Recommendations for Lacing

y s x y

Column cross-section with two components spaced s apart — lacing acts about the yy axis (the "weak" open-face direction).

  1. ryy > rxx (the built-up section is proportioned so the laced/open direction has the larger radius of gyration).
  2. Lacing should not vary throughout the length of column (ℓ, b, t, θ → fixed throughout the length).
  3. Single lacing on the opposite face should be a mirror image, and on the adjacent face it should be staggered.
At the top and bottom of a laced column, batten plate should be used.
  1. Angle of inclination of the lacing bar to the longitudinal axis of the column should be between 40° and 70°.
  2. Local-buckling safeguard:
c

c = spacing between intermediate lacing connections along one component of the column.

[crmin] (one section)≤50 [crmin] (one section)≤0.7λ (whole)

to safeguard against local buckling.

The above recommendation is for safety against local buckling.

If the criterion is not satisfied If the above criterion is not satisfied, we will increase the value of θ so that c reduces. Or, if even by increasing θ to 70°, C is reduced and even then the criterion for local buckling is not satisfied, we will adopt double lacing.

Effective Length & Slenderness of Lacing Bar

ℓeff= ℓ for single lacing 0.7ℓ for double lacing 0.7ℓ for welded lacing

ℓ → distance between inner ends of rivets or weld.

α β ℓeff β t b α

Lacing bar section b × t; β–β is the minor axis of the rectangular bar cross-section, giving the minimum radius of gyration.

Iββ=bt312 rmin=(bt3/12)bt=t12
λlacing=ℓeff(t/12)≤145
ℓlacing40 for single lacing ℓlacing60 for double lacing

Check for Safety — Force in Lacing

Lacing should be designed for shear arising due to bending moment, lateral loading, and incidental eccentricity (unavoidable eccentricity). Due to incidental eccentricity, transverse shear is taken as 2.5% of the axial loading, and this transverse shear is divided equally between parallel planes of lacing.

V/2 V/2 θ 2 V/2 1 V/2 3 V/2 4

V/2 is applied at each panel joint on the two open faces (left: elevation of one face; right: plan showing all four corners of the built-up section).

V/2 θ V/2 θ F

Resolving the transverse shear V/2 along the lacing bar's axis: F·sinθ = V/2.

Fsinθ=V2
F=V2sinθ

Design force for lacing is V/(2sinθ), where V = 2.5% of axial loading.

Check for tension

(b−d′)t×σat≥V2sinθ

if yes, safe in tension.

Check for compression

B×t×σac≥V2sinθ λ=ℓefft/12→find σσac

if yes, safe in compression.

Design for connection

V/2sinθ

Lacing bars connected to the column flange with rivets.

n=(V/2sinθ)Rv
F F F F column flange 2Fcosθ 2Fcosθ F θ θ

Two lacing bars meeting at the column flange each carry force F; their horizontal (in-line) components combine to 2Fcosθ on the connecting rivet.

for θ=45°, 2Fcosθ=2×V2sinθ×cosθ=Vcotθ

In this case the rivet will be assumed to be in single shear, and the design force will be F = V/(2sinθ), or 2Fcosθ = Vcotθ, whichever is greater (2Fcosθ governs for θ < 60°):

n=max{V2sinθ, Vcotθ}/Rv (in single shear)

(θ > 60° → V/2sinθ governs; θ < 60° → Vcotθ governs).

Worked Example — Lacing for a 2ISMC300 Column (WSM)

Design lacing for a column section designed in the previous problem (2 ISMC300). Spacing 185 mm clear; gauge g = 50 mm (if not given, taken as Cyy + 10–15 mm).

x x 185 y rxx = 118.1 mm ryy = 26.18 mm

Two ISMC300 channels back to back, toes outward, spaced 185 mm; rxx = 118.1 mm, ryy = 26.18 mm (of one channel).

For rxx = ryy of the combined section, spacing = 183.12 mm. If spacing adopted = 185 mm ⇒ ryy > rxx. OK.

Step 1

50 θ = 45° 185 C 285 mm

Adopting θ = 45° (assumed) — checking for local buckling between intermediate connections.

c=2×285=570 mm

185 + 50 + 50 = 285 mm (half-panel gives the individual-section slenderness).

Crmin (individual section)=57026.2=21.77≤50, ≤0.7×84.64
OK — safe in local buckling. No requirement of double lacing.
e ℓ e

L = ℓ + 2e, where e is the edge distance beyond the two end rivets.

inclined length=ℓ=2852=403.05 mm adopt dia of rivet=22 mm⇒bmin=66 mm⇒adopt b=70 mm tmin=ℓ40=403.0540=10.07 mm⇒adopt t=12 mm
λlacing=ℓefft/12=403.0512×12
λlacing=116.35<145 OK
force in lacing bar=V2sinθ=2.5% of(750×103)2sin45°=13.25 kN

Check for tension & compression

π2E1λlacing2=145.81 MPa σac=0.6fcc⋅fy[fcc1.4+fy1.4]1/1.4=66.435 MPa
load capacity of lacing in compression=66.43×70×12=55.8 kN>13.25 kN
OK — safe in compression.
capacity of lacing in tension=(b−d′)t×σat=(70−23.5)×150×12

assuming one rivet along width.

=83.7 kN>13.25 kN OK — safe in tension.

Design for connection

As θ = 45° < 60°, the design force will be Vcotθ:

Vcot45°=V=2.5×750100=18.75 kN
12 13.6 = T T = 13.6 mm

We adopt the smaller thickness for bearing calculation — min(12 mm lacing, 13.6 mm channel flange).

rivet value in single shear=π4×23.52×100=43.37 kN

assuming power-driven shop rivets.

bearing strength=min(12,13.6)×23.5×300=84.6 kN
Rivet value=min{43.37,84.6}=43.37 kN η=18.7543.37=0.43⇒adopt 1 rivet.

Battens

end batten effective depth of end batten effective depth of intermediate batten intermediate battens end batten solid plate C overall depth g s g ℓ

Battened column — end battens (solid plates) at top and bottom, intermediate battens spaced C apart along the length; g = edge distance, s = clear gap between battens, ℓ = distance between innermost rivet/weld lines.

  1. ryy > rxx
  2. Effective length of a battened column is taken as 10% more than the laced column.
  3. Battens on opposite faces should be a mirror image.
  4. Number of battens should be such that the column is divided into not less than 3 parts longitudinally, i.e. minimum number of intermediate battens would be 2.
Crmin (one section)≤50 Crmin (one section)≤0.7λ (whole)
b α = s + 2Cyy

α = s + 2Cyy is the overall width of the built-up section, spanning both channel centroids.

effective depth of intermediate batten≥34α ≥2b

for end battens: effective depth ≥ α, and ≥ 2b.

overall depth=effective depth+2×edge distance thickness of batten plate t≥ℓ50

ℓ = distance between innermost connecting lines of rivets or weld.

Design of Batten Plates (WSM)

Batten plate should be designed for moment and shear arising due to shear force on account of incidental eccentricity. Shear force between flange plate and shear force due to incidental eccentricity = 2.5% of axial load.

V/2 V/2 C C

V/2 applied to each open face at the C spacing between batten centres.

V/4 V/4 V/4 V/4 D ℓ VC/4 VC/4 VC/2ℓ VC/2ℓ M D t VC/2ℓ

Batten plate as a short beam spanning ℓ between the two component flanges, fixed at both ends with V/4 applied at each end (M = VC/4, Vb = VC/2ℓ).

M=VC4 Vb=VC2ℓ
Design shear force for the batten plate is VC/2ℓ, and design bending moment for the batten plate is VC/4.

For safety in shear:

average shear stress=(VC/2ℓ)D×t≤0.4fy

Maximum bending stress:

(VC4)×(D/2)(tD3/12)≤0.66fy

↑ permissible bending stress — for safety in bending.

Design moment and shear calculated above is applicable for both end and intermediate battens. However, we need to check safety of only the intermediate batten — if intermediate batten is safe, end batten will be safe.

Design for connection

Design for SF = VC/2ℓ BM = VC/4 Fp = (VC/2ℓ)/n FT = (VC/4)r / ∑Ar²

Batten-to-column rivet group carries direct shear Fp = (VC/2ℓ)/n plus torsional force FT = (VC/4)r/∑Ar² from the eccentric moment.

Fd2+FT2≤Rv for safety

Connection will be designed as an eccentric connection subjected to direct shear force of (VC/2ℓ) and torsional moment (VC/4). We will adopt number of rivets and check safety of rivets.